In this case we will change the rounding precision from 2 to 1, because there is no need to see the degrees in such detail.

Step-by-step guide

  1. Go to Config/Provisioning → Sensor Templates → Site Templates
  2. Click on Edit next to the correcponding Site Template
  3. Toggle SU/Normal Mode and clkick on the +Sensors to colapse it
  4. Click on the desired sensor. In this case Temperature
  5. In the field sensor.sensor_gateway.calibration_rule.rounding_precision.value change the value to 1
  6. Toggle SU/Normal Mode and clkick on back
  7. Now the Site Template needs to be redployed for the changes to take effect → How to deploy a Site Template

...

Info

Raw Result Factor is a calculated value, depending on the values we get from the I/O module and the temperature range the sensor can measure. In this case, the I/O module gives a value ranging from 0-32767. This needs to be divided by the range the temperature sensor can measure (-50-150°C).