Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
Check the serial of a facility:
-Login with system/admin
-Execute:   cat  grep serial /opt/azeti/SiteController/config/SiteController.cfg | grep serial 

Do a security copy of the configuration before touching it:

...

vi /opt/azeti/SiteController/config/SiteController.cfg
Some vi commands: 
press <esc> to start any command
"i" for editing
Change what you want to change
<esc>:wq  To write and exit
<esc>:q!  To exit without saving anything
<esc>dd  To delete the line where you have the cursor
Restart Site Controller:
/opt/azeti/SiteController/run_SiteController.py restart

...

/opt/azeti/SiteController/run_SiteController.py start
Stop Site Controller:
/opt/azeti/SiteController/run_SiteController.py stop
Start a module of Site Controller:
EjEg: Modbus
/opt/azeti/SiteController/run_SiteController.py start  ModbusMaster.py
Stop a single module of Site Controller:
EjEg: Modbus
/opt/azeti/SiteController/run_SiteController.py stop  ModbusMaster.py

...

# tail -f /opt/azeti/SiteController/log/ModbusMaster.log
Modbus operations
CE-AD81-34N3-0.2/ 0-10V
modpoll_ex -p none -b 9600 -t 4 -a 8 -0 -r 16 -s 1  -c  12  /dev/ttyUSB1
Modbus fuel sensor
modpoll_ex -a 1 -b 9600 -d 8 -p none -s 1 -t 4 -0 -o 3 -1 -r 01  -c 10 10.0.0.211
CE_AU11_DC_Voltagemeter (RTU)
modpoll_ex -a 7 -b9600 -d 8 -p none -0 -r 16 -t 4 -s 1 -c 1 /dev/ttyUSB1
   



Modbus daemon configuration
COM1
COM2
/dev/ttyUSB1
/dev/ttyUSB0
daemon_id 0
daemon_id 1
Check for libraries:
PYTHONPATH=/mnt/data/azeti/SiteController/lib/lib/python2.7/site-packages /mnt/data/azeti/SiteController/src/test_lib_installed.py

...

$cat output.txt | grep PAUL (if the serial of the system is PAUL - modify accordingly!)
If it is not there: script to re-search

...

Error while starting mosquitto:
Starting mosquitto ...
Traceback (most recent call last):
  File "/opt/azeti/SiteController/run_SiteController.py", line 1540, in <module>
    exit_code = main(sys.argv)
  File "/opt/azeti/SiteController/run_SiteController.py", line 1499, in main
    start_mosquitto()
  File "/opt/azeti/SiteController/run_SiteController.py", line 1026, in start_mosquitto
    '-d'])
  File "/opt/azeti/SiteController/run_SiteController.py", line 707, in start_submodule
    LOGGER.exception('Exception while trying to run command "%s":' % cmd)
AttributeError: 'NoneType' object has no attribute 'exception'
This means: mosquitto could not start. Probably due to path to mosquitto. (See above Check mosquitto configuration)
Configuration of fuel tank parameters:

...

        "timestamp": "2016-03-18T00:20:22.877Z-0500"
    }
]
Mosquitto topics:

Note:

topics in communication to and from external cloud broker (currently cloud/#hd/#sys_msg/#events/# and imgdata/#) may be required to be prefixed with the organization short name to allow an organization based autorization scheme, like so: azeti/cloud/#.

topic
description
retained
qos
related modules
calibrated_result/<sensor_id>generated by certain modules but almost the RawResultDemuxyes  
cloud/<sys_id>/exec_action/<action_id>command from the cloud to execute the specified actionno Actuatormodules like ModbusD or snmpgetd
cloud/<sys_id>/jobsreception of jobs from the cloudno JobProcessor
command/persistord/   persistord
commandresult/persistord/   persistord
config/action/<action_id> yes Actuatormodules
config/completeThe complete configuration (sensors, devices,actions,rules) as XML (retrieve from SC (subscribe))yes ConfigProvider
config/complete_updateThe complete configuration (sensors, devices,actions,rules) as XML to the SiteController (publish to)yes ConfigProvider
config/device/<device_id> yes  
config/module/<module_name>/[complete|update] yes  
config/rule/<rule_id> yes AutomationController
config/sensor/<sensor_id> yes  
events/<sys_id>/<sensor_id>generated by certain modules but almost the CalibResultsEvaluator, sent to cloud and partially to ACno cloud, AutomationController
hd/<sys_id>uncompressed historical data sent to the cloud

no, internal

yes, external

0

1

HD2CloudExporter, cloudConnector

cloudConnector, cloud

hd/<sys_id>/application/gzip

events/<sys_id>/application/gzip

compressed historical data sent to the cloud

no, internal

yes, external

0

1

HD2CloudExporter, cloudConnector

cloudConnector, cloud

imgdata/<sys_id>/<device_id>Image data, combined with description in a tar (SC-258)no http_server, cloudConnector, data_store
jobs/access_list_updatesimple job, forwarded by the JobProcessorno JobProcessor, VS_access_control
jobs/dynamic_HD_subscriptionsimple job, forwarded by the JobProcessorno 

JobProcessor, HD2CloudExporter, data_store

jobs/remote_execsimple job, executes a preconfigured shell command on SiteControllerno JobProcessor
module/<module_name>/command

example: The topic module/modbusd/command with payload statsgets returned with

the topic module/modbusd/command/reply with statistics as payload

  cloudConnector, data_store, modbusd
module/<module_name>/last_published_timestamp   HD2CloudExporter
module/state/<module_name>A module sends the internal state, useful for a better organized system startyes InternalStates, run_SiteController, Watchdog
module/state/requestWatchdog requests the states of the modules, no payload. The modules answer via InternalStatesyes Watchdog, InternalStates
raw_result/<sensor_gateway_id>generated by data acquisition modules like ModbusDyes RawResultDemux
sc/configask Matthias   
sys_msg/<sys_id>class sys_msg is defined in result.py, destination of the message is the cloud.  jobs_updateConfig, result, cloud, actuatormodules, watchdog
vs_data/<sensor_id>

specific data for a virtual sensor (currenty used by the VS to hold data during a restart).

These data should be stored in a database (persistord/data_store) and re-published if not available

on mosquitto.

yes 

VS_access_control, VS_battery_details

 

persistord, (data_store)


Username/password test systems
system/admin
To reboot a Cisco-device:
#reboot
To stop a Cisco-device:
#halt